Fault Code
Meaning
Precautions
E 101
Fault detected
while monitoring
process
Ensure that sensor
1 is connected
and oper-
value with sensor
1. Sensor
2 has taken
ating properly.
over control.
E 102
E 103
E 104
E 105
Fault detected
while monitoring
processval-
Ensure that sensor 2 is connected
and oper-
ue with sensor
2. Sensor
1 has taken
over
ating properly.
control.
Output
signal
failure
at analog
output
2 Checkcurrent
path between
pins 11 and 12.
(A02).
Check connections
and receiving
device.
Check that load is less than 650 ohms.
Check dc supply for overload
(max 1 OOmA).
Check
supply voltage
is not less than 10%
of nominal.
Check FCODE
124 set to Option
2 if A02 is not in use.
Controller
has not been tested.
It was either
Contact
your Fisher representative.
delivered
untested
or the parameter
and
function
EEPROM
has been exchanged
or
corrupted
since delivery.
Difference
between
setpoint
value and pro-
Bring process value and setpoint value clor
cess value when autotuning
started
is too
er to each other, then restart autotuner
func
large. Tuning
started
with output signal too
tion. Retune
at level between
10 and 90%.
close
to 0% or 100%.
Tuning
function
is
I
aborted
E 106
E 107
E 108
WARNING:
Process
noise level too high or A process
load upset during
early tuning.
process
not stable
enough
for autotuner
Switch controller
to manual
mode and stabi-
function
to operate
properly.
This is only a lize process,
or filter the process value. Re-
warning,
the controller
continues
to tune,
tune.
but results may not be optimum.
WARNING:
Disturbance
has occurred
in Check PID parameters
and possibly
retune
the process during a tuning procedure.
Tun-
the controller
as the parameters
may not be
ing function
continues,
but results
may not optimum.
be optimum.
Tuning
procedure
has
exceeded
the
None required.
Controller
automatically
re-
32-hour maximum
limit. This is a fatal tuning
turns to the state it was in before the user
error and tunina
has been aborted.
started
the autotuner.
UM6.1:DPf?900;9147