Fisher DPR900 User Manual page 80

Integral controller
Table of Contents

Advertisement

5-26
Configuration
(FISHER"]
Function
Parameters
FCODE
Range
Unit
Increment
Default
Selected
V&N?
Value
Extra
Setpoint
value
12
MSIS.
a"Y
1 digit
Min
Internal
Range
Setpoint
FCODE
12 defaults
to the lower measuring
range
value as set in FCODE
24.
Function
FCODE
OptIon
NO
Default
Selected
V&e
Value
Automatic
142
Disabled
1
1
Setpoint
Switches
to remote setpoint
2
Switchmg
Switches
to extra internal
setpoint 3
The ESP is functionally
a RSP. The R button LED remains
lit when
this setpoint
is active,
as a reminder
that manual
setpoint
entry is not
possible.
If FCODE
142 is set to Option
3, switching
to extra internal
setpoint
enabled,
the extra internal
setpoint
is displayed
in the remote
mode.
Simply
press one of the green setpoint
increase/decrease
buttons
to view the current
digital value of ESP when active.
The local setpoint
can be made to track both ESP and RSP. Switching
can be done manually
or using a discrete
input signal.
FCODE
140 is
used in this case, however
the ESP replaces
the RSP in the
description.
Select the LSP tracking
option using FCODE
140.
Function
FCODE
Option
NO
Default
Selected
Value
Value
Setpornt
140
Disabled
1
1
Tracking
Tracks remote setpomt (RSP/ESP)
2
WY
Tracks PV ,n Manual
3
The manual
button
overrides
both the remote
and
extra internal
setpoints,
when they are active.
When the controller
is in the manual
mode, the
local setpoint
can be set but is not in use.
UM61:DPR900:9102
Change
1 -September
1991