Fisher DPR900 User Manual page 50

Integral controller
Table of Contents

Advertisement

3-14
Controls
and Indicators
[FISHER")
Clearing
an error code upon entering
the
configuration
mode, may not clear the code due to
required
configuration
changes.
Upon completion
of these changes
and exiting
the programming
mode, the original
error code may still be
observed.
Re-enter
the configuration
mode a
second
time to clear the error.
3.12
Bumpless
Transfer
Switching
between
Auto and Manual
is bumpless
(unchanged)
in both
directions.
This does not apply if the DPRSOO
is used as a simple
proportional
(P) controller.
In a P controller,
the output signal in Auto is
always 50% when the process
value is equal to the setpoint
value.
Deleted
Change
7 -September
7991

Hide quick links: