Fisher DPR900 User Manual page 52

Integral controller
Table of Contents

Advertisement

4.2.1
FCODE
24,25
and 26 must be set for the
appropriate
measuring
ranges
before any other
FCODE
is selected.
This is because
many other
parameters
use the measuring
range limits as
reference.
If the measuring
range is altered,
related
limits and alarms
are automatically
adjusted
to suit the new range. (This does not
apply to cases where the DPRlOO
Temperature
Input Module
is used since its measuring
range is
set automatically
with FCODE
118.
Tuning
parameter
setting
and configuration
function
selection
take
place in the configuration
mode.
Press the PROG
button to enter the configuration
mode.
Pressing
the
PROG
button
illuminates
the red light in the button and the red
STORE
and SET lights. These
lights indicate
that the secondary
functions
of the R and TUNE
buttons
are active.
If the controller
is set for authorization
check (FCODE
139), the
configuration
values
may be read only when the STORE
light is Off
Most configurable
controller
functions
and tuning
parameters
can be
changed
while the controller
is operating.
For safety, vital controller
functions
cannot
be altered
during operation.
The controller
must be
in the Manual
mode to change
any functions
with FCODE's
greater
than 100. When
changes
are made during configuration,
either the
SET or STORE
light flashes,
indicating
the appropriate
action to be
taken.
A complete
list of FCODE's
is provided
in Section
5.
Tuning Parameter/Configuration
Changes
The authorization
check can be temporarily
disabled
(without
changing
FCODE
139) by
pressing
the R button immediately
after pressing
the PROG
button in Step 1.
UM6.1:DPf?900:9102
May 1991