3-10
Controls and Indicators
[FISHER"]
3.6.3
3.7
The Local setpoint
cannot
be changed
while the
controller
is in the remote
mode. If the user
attempts
to change
the setpoint
value in the
remote
mode, the controller
flashes
ERROR
Switching
Between Remote and Local
Setpoints
Switch from the RSP, CSP or ESP mode to the LSP mode by using an
external
digital
signal
or
switch manually,
using the R (remote)
button.
Manual
switching
via the R (remote)
button always overrides
the
digital
signal or RS-485
signal. Remote/Local
switching
occurs only if
the controller
is in the Remote
mode.
Changing
Configured
Values:
Ratio,
Bias and Extra Internal
Setpoint
The RSP input value received
at Al2 can be configured
to be modified
before being used as the controller's
RSP.
Al2
FCODE 120
_
FCODE 1
FCODEZ
__
Use FCODE
1 and 2 to adjust the ratio and bias values
used in
conjunction
with the RSP or the internal
calculation
functions
(FCODE
107 and 108). Both values
reside within the controller
configuration
parameters;
therefore
the user must enter the configuration
mode to
change
these values.
Press the PROG
button to enter the
configuration
program.
Then use the TUNE
button to advance
to the
appropriate
FCODE.
After each FCODE
number,
the controller
indicates
the current
value stored.
Use the increase/decrease
buttons
(11) to change
the value.
Press the flashing
R button to save the new
value.
Function
Parameter
FCODE
Range
Unit
Increment
Default
Selected
Value
Vallle
Ratio
Gain
1
0-9.99
-
0.01
1
Bias
zero level offset
2
+I- M
a"Y
1 digit
0
lJM61:DPR900:9102
May 1991