Configuration
5-7
The resolution
is the measuring
range shown in
the following
table, divided
by 4000. The resolution
will not be improved
by using limits other than
those in the table.
Even though
the stated
resolution
is fractional,
the digital
display
only
shows degrees
in whole numbers.
Module
Degrees
F
Degrees
c
TYPO
Range
Resolution
Range
Resolution
100ohmRTD
-56-1112
0.29 degrees
50
- 600
0.16 degrees
TYPO
J
32 - 1472
0.36 degrees
O-600
0.20 degrees
TYPO K
32 - 2372
0.56 degrees
0 - 1300
0.32 degrees
TYPO R
32 - 2732
0.67 degrees
0 - 1500
0.37 degrees
Tvpe S
32 - 2732
0.67 degrees
0
1500
0.37 degrees
I
I
Examples:
A Type R Thermocouple
sensor with a DPRIOO
Temperature
Input
Module
has a sensing
range of 0 to 1500X.
The measuring
range
is 0 to 5OO'X,
set with FCODE
24 thru 26. The controller
sees only
that portion of the sensor signal lying within the defined
measuring
range. The digital
display
now shows temperature
between
0 and
5oooc.
The displays
can now be further limited
by using the setpoint
limiting
function
to limit the maximum
setpoint
range (FCODE
106, 9, IO) to
0-300°C.
If setpoint
limits of O°C and 300°C
are entered,
the digital
70
display
indicates
exact temperatures
between
0 and 500°C,
butthe
60
50
bargraph
indicates
O°C at 0% abd 300°C
at 100%. At 70% on the
40
bargraph,
the temperature
is 210°C.
30
20
10
0%
May 7997
UM6.1~DP/?900:9102