Integral controller
Table of Contents

Advertisement

5-34
Configuration
(FISnER;
I
I
I
0%
Manual 1
Auto
AU10
t Time
t0
t1
k!
DPR900433
The heating
time is 7 hours (420 minutes)
and:
n
The measuring
range is -50 to 600 degrees
C,
n
The current
process
value is 90 degrees
C
H
The final setpoint
value is 300 degrees
C.
The process
must heat to 210 degrees
C in 420 minutes,
giving a
ramp of 0.50 degrees
C/minute.
The figure shows the heating
time
between
to and tl.
At to the setpoint
value equals the process
value. The controller
ramping
algorithm
moves the setpoint
value at a constant
speed to
the preset value during to to tl. The PID parameters
are not
influenced
by the ramp speed,
and the actual value follows the
changing
setpoint
value throughout
the ramping.
The ramp starts when the controller
switches
from manual
to auto, to,
When the controller
is switched
to auto, the setpoint
ramping
starts at
the present
process
value, moving
at the preset speed towards
the
final setpoint.
DO3 and DO4 indicate
the ramp status when FCODE
109 is set to 1.
DO3 is active during ramping,
from to to t,. DO4 is active at tz,
indicating
that the configured
time period
is elapsed.
While the ramp is in control,
the digital
display
shows the
instantaneous
value of either the process
value or the setpoint,
depending
on the configuration.
The final setpoint
value displays
as a
brighter
bar on the bargraph
and the PV and SP bargraphs
also show
the instantaneous
values.
To alter the setpoint
value while the ramp is active,
switch the
controller
to manual
mode.
Insert the new setpoint
value and restart
the ramp with the new parameters.
lJM6.1:LlPR900:9147
Change
2 -July
1992