Selecting Gain Scheduling - Fisher DPR900 User Manual

Integral controller
Table of Contents

Advertisement

5-50
Configurafion
[FISHER"]
H
The first tuning, for the case where the reference
signal is in the
lowest range, O-33 percent,
is complete
and the derived
PID
values
are stored in all levels (FCODE
36,37,36),
(39,40,41)
and
(42,43,44).
Function
Parameters
PID
Pa-
Gain
ram&r
1 Ti (Reset)
Td (Rate)
FCODE
Range
Unit
Increment
Default
Selected
V&K2
Value
i;
0.01-99.99
-
0.01
0.01
OFF-9999
s
IS
1000s
38
o-9999
s
IS
0
H
The tuning for the second
range (33-67
percent)
is complete
after
values
have been derived
at reference
signal
level 2. The derived
values
for this range are also stored as the values
for the third
level (FCODE
39,40,41)
and (42,43,44).
5.11.2
Selecting
Gain Scheduling
Function
Parameters
PID
Pa-
Gain
rameter
2
Ti (Reset)
Td (Rate)
FCODE
Range
Unit
Increment
Default
Selected
Value
Value
39
0.01-99.99
-
0.01
0.01
40
OFF-9999
s
IS
1000s
41
o-9999
s
IS
0
n
The reference
signal
has increased
to range 3 (67-i 00 percent)
and tuning
is complete.
The values for this range are stored in the
third level (FCODE
42,43,44).
Function
Parameters
PID
Pa-
Gain
rameter 3
Ti (Reset)
Td (Rate)
FCODE
Range
Unit
Increment
Default
Selected
Value
Value
42
0.01-99.99
-
0.01
0.01
43
OFF-9999
s
IS
1000s
44
o-9999
s
1s
0
n
A further
tuning has been done when the reference
signal
returned
to range 2. The system
remembers
that the tuning
has
been performed
at all levels, so that only values
at level 2 are
changed.
If gain scheduling
is deactivated
during
operation,
the controller
will fill
the parameter
with the active set of PID terms at all levels.
Use FCODE
34 and 35 to set the breakpoints
between
the three
ranges,
if the default
breakpoints
are not appropriate.
Function
Parameters
FCODE
Range
Unit
Increment
Default
Selected
Value
Value
Gain
LOW3
34
O-100
%
1%
33%
Scheduling
UPPer
35
O-100
%
1%
67%
Breakpoints
May 7991