Maximum Cable Capacitance

The maximum cable length for HART communication
is limited by the characteristic capacitance of the
cable. Maximum length due to capacitance can be
calculated using the following formulas:
Length(ft) = [160,000 − C
Length(m) = [160,000 − C
where:
160,000 = a constant derived for FIELDVUE
instruments to ensure that the HART network RC time
constant will be no greater than 65 μs (per the HART
specification).
C
= the capacitance of the control system or
master
HART filter
C
= the capacitance of the cable used (see table
cable
2-2)
The following example shows how to calculate the
cable length for a Foxboro
with a C
of 50, 000 pF and a Belden 9501 cable
master
with characteristic capacitance of 50pF/ft.
Length(ft) = [160,000 − 50,000pF] [50pF/ft]
Length = 2200 ft.
22
No
Install the digital
valve controller to
valve controller.
the HART Tri-Loop.
Channel 2 and 3 wires
from HART Tri-Loop
to the control room.
Figure 2-12. HART Tri-Loop Installation Flowchart
(pF)] [C
(pF/ft)]
master
cable
(pF)] [C
(pF/m)]
master
cable
t
I/A control system (1988)
A
Install the HART
Tri-Loop. See
HART Tri-Loop
product manual
to receive digital
burst commands
Mount the
HART Tri-Loop
to the DIN rail.
Wire the digital
Install Channel 1
wires from HART
Tri-Loop to the
control room.
(Optional) Install
B
The HART communication cable length is limited by
the cable characteristic capacitance. To increase
cable length, select a wire with lower capacitance per
foot. Contact your Emerson Process Management
sales office for specific information relating to your
control system.
Installation in Conjunction with a
Rosemountt 333 HART Tri-Loop

HART-to-Analog Signal Converter

Use the DVC6200 digital valve controller in operation
with a Rosemount 333 HART Tri-Loop
HART-to-Analog Signal Converter to acquire an
independent 4-20 mA analog output signal for the
analog input, travel target, pressure, or travel. The
HART Tri-Loop accepts any three of these digital
signals and converts them into three separate 4-20
mA analog channels.
Refer to figure 2-12 for basic installation information.
Refer to the 333 HART Tri-Loop HART-to-Analog
Signal Converter Product Manual for complete
installation information.