S E R V I C E M O D E
Service mode when activated disables dialler reporting,
prevents all alarms and prevents all users from arming the
system.

Turning Service Mode ON

1) Enter programming mode.
[1][2][3][4] + [MENU]
2) Turn service mode on.
[MENU] [7][0][8]
3) Follow display prompts.
4) Hold down [MENU] to exit.
i
Keypads will display the word "SERVICE" in the middle
of the display when service mode is active.
Note

Turning Service Mode OFF

1) Enter programming mode.
[1][2][3][4] + [MENU]
2) Turn service mode on.
[MENU] [7][0][8]
3) Follow display prompts.
4) Hold down [MENU] to exit.
You must exit Service Mode to reactivate the system.
i
Service mode will automatically exit after 2 hours.
Note
D E FAU LT I N G T H E S YS T E M
Defaulting the system will reset all programming options
back to the factory default setting. All programming
information will be erased.

Hardware Default

1) Remove all power to the system - AC and battery.
2) Press and hold the default push button, then apply
power to the control panel.
3) Release the default button, The panel will reset and
revert to normal operation when default is
complete.

Software Default

1) Enter programming mode.
[1][2][3][4] + [MENU]
2) Select factory default option.
MENU 7-0-4
3) The panel will reset and revert to normal operation
when the default is complete.
An optional CM255B Default Key may be purchased
i
to unlock both the Installer PIN and RAS Security
Note
PIN. The default key is single use only. Refer to the
CM255B instructions for additional information.
Bosch Security Systems 07/14 BLCC610I
Solution 6000
Installation Manual
You can disable factory defaulting using MENU 7-7-
i
4. If factory defaulting has been disabled you must
Note
know the installer PIN to perform a factory default
otherwise the system will need to be returned to
your supplier for defaulting or you can purchase a
CM255B Default Unlock Key which will unlock the
panel in the field. Charges will apply for defaulting if
returned to the distrubutor.
T R I G G E R I N G A D U R E S S A L A R M
If your PIN is 2580, to send a duress report when the area is off,
Enter, [2][5][8][0] + [8][0] + [OK] or [ON].
If your PIN is 2580, to send a duress report when the area is on,
Enter, [2][5][8][0] + [8][0] + [OFF].
Duress alarms are triggered by entering the user PIN
i
followed by the last 2 digits of the user PIN followed
Note
by the ON or OFF key.
D O M E S T I C T E M P L AT E D E FAU LT S
The following table list the changes that will occur when
you select domestic default. See MENU 7-0-3 — Domestic
Default.
Program Option
All Trouble Reports
All Bypass Reports
All Restore Reports
Destination 1 TX Format
Access Route
Open / Close Reports
Test Route
System Route
Table 15: Domestic Reporting Defaults
D I R E C T L I N K P R O G R A M M I N G
The panel can be programmed via the Solution Link™
Upload/Download software in either Direct Link or
Remote Link modes. For Direct Link you will need a CM900
Direct Link module which is used to connect the panels
serial port to the PC.
Once the cable is connected you will need to hold down
the default switch on the panel for 5 seconds to initiate
the programming session. See the board layout drawings
in Section 3 of this manual for the default switch location.
Programming Overview
Domestic Default Value
Disabled
Disabled
Disabled
Domestic Reporting
Log Only
Log Only
Log Only
Log Only
4-3