Alarm L/Fail If Off; Digital Line; Low Voltage; Display On Line - Bosch solution 6000 Installation Manual

Hide thumbs Also See for solution 6000:
Table of Contents

Advertisement

Solution 6000
Installation Manual
the panel is able to report this signal via an alternative
reporting method such as the GSM cellular network.
If no alternative route exists then the panel will send the
signal and restore when the PSTN line is reconnected.
Alarm L/Fail If On
This option sets the panel to trigger an alarm when the
telco line fails provided that the area is turned All On or
Part On. In a multi-area system this option is global and
will be triggered if only one area in the system is in the
armed state. The alarm will continue to sound until a
valid PIN is entered or the siren timer expires.

Alarm L/Fail If Off

This option sets the panel to trigger an alarm when the
telco line fails provided that the area is turned OFF or
disarmed. In a multi-area system this option is global and
will be triggered if only one area in the system is in the
disarmed state. The alarm will continue to sound until a
valid PIN is entered or the siren timer expires.

Digital Line

If you are having issues reporting or with RAS
connections and the system is connected to a VOIP or
NBN digital line then you should set the Digital Line
option to yes.
This option has been added in version 2.15.
i
Note

Low Voltage

If the PSTN line voltage at the panel when the dialler is
on line is below 6 volts DC then you should set the Low
Voltage option to yes.
This option has been added in version 2.15.
i
Note

Display On Line

This option allows the keypad to display Phone In Use
when the telephone line has been looped by the control
panel for either incoming or outgoing calls. If this option
is disabled, no indication is provided on the keypad.
i
The dialler status indicator LED located on the main
panel will always show the status of the dialler. See
Note
Section 3 - Wiring Diagrams for more information.
9-8
Comms Programming
Comms > Properties >

Country

(*** System Wide Parameter ***)
Ln1 AUSTRALIA
Ln2 NEW ZEALAND
Ln3 ITALY
Ln4 GREECE
Ln5 CYPRUS
Ln6 SPAIN
Ln7 PORTUGAL
Ln8 HUNGARY
This menu automatically sets the dialling parameters
including dial and busy tones etc. for the country the
panel is working in.
1) Press [MENU] + [5] + [2] + [3]. The keypad will
display the currently selected country. The default
country is Australia.
2) Use the up and down arrow keys to select the
appropriate country then Press [OK].
Ln1 AUSTRALIA
Ln2 NEW ZEALAND
Ln3 ITALY
Press  OK or MENU
3) Press [OK] to confirm and save and exit or press
[MENU] to exit without saving.
WARNING: Press OK to set
dialler to
AUSTRALIA
For correct dialler operation, you must make sure
i
that the correct country selection is made for your
Note
location. If your country is not listed here please
contact your distibutor.
MENU 5-2-3
Ln9 CZECH REPUBLIC
Ln10 POLAND
Ln11 TURKEY
Ln12 CHINA
Ln13 HONG KONG
Ln14 MALAYSIA
Ln15 BRAZIL
Bosch Security Systems 07/14 BLCC610I
0