System Testing; Battery Test - Bosch solution 6000 Installation Manual

Hide thumbs Also See for solution 6000:
Table of Contents

Advertisement

S YS T E M T E S T I N G
System > System Testing >
Walk Test All Zones
This menu allows you to test all zones within an area at the
same time.
1) Press [MENU] + [7] + [9] + [0]. The keypad will
display a list of areas that are available to walk test
zones.
2) Using the up and down arrow keys, select the area
that you want to walk test, then press [OK].
Alternatively, you can enter the area number, then
press [OK]. The keypad will begin to scroll all zones
that need to be tested.
To test Zn1
open then close
Zone 1 Name
Press OK or MENU
3) Open and close each zone that needs to be tested.
A zone that has been successfully tested will no
longer scroll on the keypad display. When all zones
have been tested, the keypad will display.
All zones have been
successfully tested
Press OK or MENU
4) Press [OK] to save and exit or press [MENU] to exit
without saving.
Bosch Security Systems 07/14 BLCC610I
-
-
MENU 7-9-0
Solution 6000
Installation Manual
System > System Testing >

Battery Test

This menu allows you to test the panels standby battery.
The battery test will last about two minutes and the
keypad will display the voltage of the battery during the
test.
1) Press [MENU] + [7] + [9] + [1]. The keypad will
display the battery voltage whilst under test:
Battery test in progress.
Please wait..
Voltage = 13.4V
To Go Back Press OK
If the battery has passed the test, the keypad will
display:
Battery Test Passed
Press OK To Continue
To Go Back Press OK
If the battery has failed the test, the keypad will
display:
Battery Test Failed
Please Call For Service
To Go Back Press OK
2) Press [OK] to exit.