he control panel is capable of controlling up to 144
inputs in either hardwire and/or wireless configuration.
Each input can have its own unique name up to 20
characters to identify it on the system for display and
reporting purposes.
Under the commands menu you are able to view the
status of any input, bypass a zone, define which zones will
operate in chime mode, define which zones operate in
part 2 mode and reset smoke detectors.
There is a command called 'Zone Array' that allows the
installer to view the condition of inputs in banks of 16.
This is extremely helpful when commissioning a system
or fault finding.
There are numerous configurations for each hardwire
input. The end of line resistor can be configured to
eliminate the need to change the end of line resistors on a
ZO N E A S S I G N M E N T S
Address Setting
Module
Number
SW1 SW2 SW3 SW4 SW5
Control Panel
1 =
OFF OFF OFF OFF OFF
2 =
ON OFF OFF OFF OFF
3 =
OFF ON OFF OFF OFF
4 =
ON
ON OFF OFF OFF
5 =
OFF OFF ON OFF OFF
6 =
ON OFF ON OFF OFF
7 =
OFF ON
8 =
ON
ON
Bosch Security Systems 07/14 BLCC610I
Zone Assignment Table
Zone
Numbers
(Single EOL)
1 - 8
17 to 24
33 to 40
49 to 56
65 to 72
81 to 88
97 to 104
ON OFF OFF
113 to 120
ON OFF OFF
129 to 136
Table 20: Zones Assignments To Modules

Input Programming

job when doing a change over. Input zones can be setup
as alarm only, alarm + tamper or even split end of line.
For normally open contacts the system is wired exactly
the same as for normally closed but there is an option
provided that inverts the sealed state of a zone.
When arming the system, all zones will be tested by default
and you may wish to turn this option off for certain zones
so that you don't continually alert the operator during
arming.
The sensor watch feature lets you monitor zones to ensure
that they are working and detecting movement within a
determined programmable period.
Zones by default can be bypassed and you should disable
this option for zones you don't want to be able to bypass,
for example 24hr, fire, holdup or panic zone types.
Zone
Single or Alarm
Numbers
+ Tamper EOL
(Alarm+Tamper
With CM705B +
EOL)
CM707B Module
1 - 8
17 to 24
33 to 40
49 to 56
65 to 72
81 to 88
97 to 104
113 to 120
129 to 136
S E C TIO N 7
Zone
Numbers
(Split EOL)
N/A
1 - 16
17 to 24
17 to 32
25 to 32
33 to 40
33 to 48
41 to 48
49 to 56
49 to 64
57 to 64
65 to 72
65 to 80
73 to 80
81 to 88
81 to 96
89 to 96
97 to 104
97 to 112
105 to 112
113 to 120
113 to 128
121 to 128
129 to 136
129 to 144
137 to 144
7-1