Event Log (Operating Messages) - Siemens siprotec 7SA522 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

7.1.1.2

Event Log (Operating Messages)

From the
Device Front
:
From PC with
®
DIGSI
4
7SA522 Manual
C53000-G1176-C119-2
Operating messages contain information that the device generates during operation
and about the operation. Up to 200 operating messages are stored in chronological
order in the device. New messages are added at the end of the list. If the memory has
been exceeded, then the oldest message is overwritten for each new message.
Faults in the power system are indicated with "1HWZRUN )DXOW" and the present fault
number. The fault messages (7ULS /RJ) contain details about the history of faults.
This topic is discussed in Sub-section 7.1.1.3.
All predefined operating messages are listed and explained in a table in the Appendix.
In a specific case, of course, only the appropriate messages appear in the display. The
appendix also shows whether the message is only issued as "ON" (to indicate an
event), or as "ON" and "OFF" (to designate the beginning and end of a condition).
With the device ready for operation, first press the
The first menu item (Annunciation) is marked.
Press the
key to enter the ANNUNCIATION menu (see Figure 7-1).
Here, select the menu item Event Log (already marked). The EVENT LOG table ap-
pears.
If no messages are present, then the text "OLVW LV HPSW\" appears. Otherwise im-
portant events and changes in conditions are listed in chronological order (see Figure
7-3 as an example). Upon entering the menu, the newest (last) message is displayed
at first. The applicable date and time are noted in the display line directly above the
message. If the memory for the operating messages is not full, then the end of the en-
tries is indicated by "(1'".
(9(17 /2*

 
5HVHW /('
Example of an operating message
Figure 7-3
The [
and
keys can be used to move up and down in the Event Log.
Press the
key to return to the MAIN MENU.
MENU
Click on $QQXQFLDWLRQ. The options appear in the data window (Figure 7-4).
Double click on the desired message group in the data window, in this case Event Log.
A date and time appear in the data window as shown in Figure 7-4.
Double click on the date and time and the contents of the message group are dis-
played in another window.
MENU
key. The MAIN MENU appears.

21
in the operating field of the device
Control During Operation
7-5

Hide quick links: