Siemens siprotec 7SA522 User Manual page 475

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

To Reassemble
the Device
o
o
o
o
o
o
o
7SA522 Manual
C53000-G1176-C119-2
Terminating resistors
Jumper
Connected
X3
1-2
X4
1-2
Figure 8-12 Location of the Jumpers for Configuring the Profibus–Interface Terminating
Resistors
To reassemble the device, proceed as follows:
Carefully insert the boards into the case. The installation locations of the boards are
shown in Figure 8-7 and 8-8.
For the model of the device designed for surface mounting, use the metal lever to in-
sert the CPU board. The installation is easier with the lever.
First insert the plug connectors on the ribbon cable in the input/output modules I/O and
then on the processor module CPU. Be careful not to bend any of the connecting pins!
Do not use force!
Insert the plug connector of the ribbon cable between the processor module CPU and
the front cover in the socket on the front cover.
Press the latches of the plug connectors together.
Replace the front cover and secure to the housing with the screws.
Replace the covers.
Re-fasten the interfaces on the rear of the device housing.
This activity is not necessary if the device is for surface mounting.
C53207-A322-
Disconnected
)
2-3*
)
2-3*
)
*
Factory Set
Installation and Commissioning
2 3 4
B100
B101
3
2
1
X4
3
2
1
X3
8-19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sa522

Table of Contents