Preset Configurations

Presettings
7SA522 Manual
C53000-G1176-C119-2
User defined pulse values derived from the measured values may be configured into
the metered value window so that they may be displayed at the front relay panel.
Retrieving the configurations is also possible from the device front. You may access
configuration information under 0DLQ 0HQX: → 6HWWLQJV → 0DVNLQJ ,2 .
The menu title 0$6.,1* ,2 appears in the title bar. Configuration information re-
garding each (physical) input and output is indicated in the display.
Any new user defined information is also shown in the display once loaded into the
®
relay from DIGSI
4.
When selecting the 0$6.,1* ,2 menu, either binary inputs, LEDs, or binary out-
puts may be selected. Selection of binary inputs is illustrated in Figure 5-25.
0$6.,1* ,2

!%LQDU\ ,QSXWV
!/('
%LQDU\ 2XWSXWV ²!
Figure 5-25
Reading the configuration in the front display of the device — example
Information regarding a binary input may be displayed by using the navigation keys to
select the binary input. See Figure 5-26.
%,1$5< ,1387

!!5HVHW /(' 63
6WDWXV DW 7HUPLQDO
Figure 5-26
Selection of binary input 2 — example
In the example of Figure 5-26, information is displayed regarding binary input 2. The
display for binary input 2 indicates that it is configured as reset of the latched LEDs
using a single point indication with voltage active (High). The present conditions of bi-
nary input 2 is also given as 0 (not active). If a binary input is active, a 1 is displayed.
Assignment of LEDs may be indicated at the relay, itself, using a replaceable labelling
strip with plain text on the front panel located, directly next to the LEDs.
The LED indication presettings which are present in the device when it leaves the fac-
tory are summarised in Table 5-4, those of the binary inputs in Table 5-5. The output
relay pre-configuration is shown in Table 5-6. The outputs R1 to R7 in this case are
particularly suited for fast operation.

²!

²!



+

Configuration
%,1$5< ,13876


!%LQDU\ ,QSXW ²!
²
5-27