Trip Circuit Supervision; Settings - Siemens siprotec 7SA522 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

Functions

6.16.3 Settings

Measurement Su-
pervision
Addr.
Setting Title
2901
MEASURE.
SUPERV
2902
BALANCE U-LIMIT
2903
BAL. FACTOR U
2904
BALANCE I LIMIT
2905
BAL. FACTOR I
ΣI THRESHOLD
2906
ΣI FACTOR
2907
2910
FUSE FAIL MON.
2911
FFM U>(min)
2912
FFM I< (max)
2913
FFM U<max (3ph)
2914
FFM Idelta (3p)
2921
T mcb
Trip Circuit
Supervision
Addr.
Setting Title
4001
FCT TripSuperv.
4002
No. of BI
4003
Alarm Delay
6-228
The indicated secondary current values for setting ranges and default settings refer to
I
= 1 A. For the nominal current 5 A the current values are to be multiplied by 5. The
N
values of impedance are divided by 5.
Setting Options
ON
OFF
10..100 V
0.58..0.95
0.10..1.00 A
0.10..0.95
0.05..2.00 A
0.00..0.95
ON
OFF
10..100 V
0.10..1.00 A
2..100 V
0.05..1.00 A
0..30 ms
Setting Options
ON
OFF
1..2
1..30 sec
Default Setting
ON
Measurement Supervision
50 V
Voltage Threshold for Balance
Monitoring
0.75
Balance Factor for Voltage
Monitor
0.50 A
Current Balance Monitor
0.50
Balance Factor for Current Moni-
tor
0.10 A
Summated Current Monitoring
Threshold
0.10
Summated Current Monitoring
Factor
ON
Fuse Failure Monitor
30 V
Minimum Voltage Threshold U>
0.10 A
Maximum Current Threshold I<
5 V
Maximum Voltage Threshold U<
(3phase)
0.10 A
Delta Current Threshold
(3phase)
0 ms
T mcb
Default Setting
OFF
TRIP Circuit Supervision is
2
Number of Binary Inputs per trip
circuit
2 sec
Delay Time for alarm
Comments
Comments
7SA522 Manual
C53000-G1176-C119-2