Test Messages To The System (Scada) Interface During Test Operation - Siemens siprotec 7SA522 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

7.2.3

Test Messages to the System (SCADA) Interface during Test Operation

7SA522 Manual
C53000-G1176-C119-2
Double click on &KDQJH *URXS. The &KDQJH *URXS window is opened, as shown
in Figure 7-33.
Figure 7-33
Setting group switching in
The active setting group is displayed. To switch to another setting group, click on the
field 9DOXH and select the desired option from the drop-down list. Before closing the
window, transfer the change to the device. This is done by clicking on the button
'LJVL  'HYLFH. A request for Password No. 7 (password for setting groups) is giv-
en. Enter the correct password, and then click on 2..
Depending on the type of protocol, all messages and measured values transferred to
the central control system can be identified with an added message "test operation"-
bit while the device is being tested onsite (test mode). This identification prevents the
messages from being incorrectly interpreted as resulting from an actual power system
disturbance or event. As another option, all messages and measured values normally
transferred via the SCADA interface can be blocked during the testing (block data
transmission).
A password for test and diagnostics is required (password no. 4) to block the messag-
es and measured values.
Data transmission block can be accomplished by controlling binary inputs, by using
the operating panel on the device, or via DIGSI
If binary inputs are used, then the appropriate inputs must be configured.
Control During Operation
®
4.
7-29