Appendix
Addr.
Setting Title
1243
R load (Ø-Ø)
ϕ load (Ø-Ø)
1244
1301
Op. mode Z1
1302
R(Z1) Ø-Ø
1303
X(Z1)
1304
RE(Z1) Ø-E
1305
T1-1phase
1305
T1-1phase
1306
T1-multi-phase
1306
T1-multi-phase
1306
T1-multi-phase
1307
Zone Reduction
1311
Op. mode Z2
1312
R(Z2) Ø-Ø
1313
X(Z2)
1314
RE(Z2) Ø-E
1315
T2-1phase
1315
T2-1phase
1316
T2-multi-phase
1316
T2-multi-phase
1317
Trip 1pole Z2
1317
Trip 1pole Z2
1321
Op. mode Z3
1322
R(Z3) Ø-Ø
1323
X(Z3)
B-6
Function
Setting Options
Distance protec-
0.10..250.00 Ohm
tion, general set-
tings
20..60 °
Distance protec-
tion, general set-
tings
Distance zones
Forward
(quadrilateral)
Reverse
Non-Directional
Inactive
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.00..30.00 sec
(quadrilateral)
Distance zones (
0.00..30.00 sec
MHO)
Distance protec-
0.00..30.00 sec
tion, general set-
tings
Distance zones
0.00..30.00 sec
(quadrilateral)
Distance zones (
0.00..30.00 sec
MHO)
0..30 °
Distance zones
(quadrilateral)
Distance zones
Forward
(quadrilateral)
Reverse
Non-Directional
Inactive
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.00..30.00 sec
(quadrilateral)
Distance zones (
0.00..30.00 sec
MHO)
Distance zones
0.00..30.00 sec
(quadrilateral)
Distance zones (
0.00..30.00 sec
MHO)
Distance zones
NO
(quadrilateral)
YES
Distance zones (
NO
MHO)
YES
Distance zones
Forward
(quadrilateral)
Reverse
Non-Directional
Inactive
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Distance zones
0.05..250.00 Ohm
(quadrilateral)
Default Setting
1; Ohm
R load, minimum Load Impedance (ph-
ph)
45 °
PHI load, maximum Load Angle (ph-
ph)
Forward
Operating mode Z1
1.25 Ohm
R(Z1), Resistance for ph-ph-faults
2.50 Ohm
X(Z1), Reactance
2.50 Ohm
RE(Z1), Resistance for ph-e faults
0.00 sec
T1-1phase, delay for single phase
faults
0.00 sec
T1-1phase, delay for single phase
faults
0.00 sec
T1multi-ph, delay for multi phase faults
0.00 sec
T1multi-ph, delay for multi phase faults
0.00 sec
T1multi-ph, delay for multi phase faults
0 °
Zone Reduction Angle (load compen-
sation)
Forward
Operating mode Z2
2.50 Ohm
R(Z2), Resistance for ph-ph-faults
5.00 Ohm
X(Z2), Reactance
5.00 Ohm
RE(Z2), Resistance for ph-e faults
0.30 sec
T2-1phase, delay for single phase
faults
0.30 sec
T2-1phase, delay for single phase
faults
0.30 sec
T2multi-ph, delay for multi phase faults
0.30 sec
T2multi-ph, delay for multi phase faults
NO
Single pole trip for faults in Z2
NO
Single pole trip for faults in Z2
Reverse
Operating mode Z3
5.00 Ohm
R(Z3), Resistance for ph-ph-faults
10.00 Ohm
X(Z3), Reactance
Comments