Siemens siprotec 7SA522 User Manual page 203

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

Addr.
Setting Title
1356
T1B-multi-phase
1357
1st AR -> Z1B
1311
Op. mode Z2
1312
R(Z2) Ø-Ø
1313
X(Z2)
1314
RE(Z2) Ø-E
1315
T2-1phase
1316
T2-multi-phase
1317
Trip 1pole Z2
1321
Op. mode Z3
1322
R(Z3) Ø-Ø
1323
X(Z3)
1324
RE(Z3) Ø-E
1325
T3 DELAY
1331
Op. mode Z4
1332
R(Z4) Ø-Ø
1333
X(Z4)
1334
RE(Z4) Ø-E
1335
T4 DELAY
1341
Op. mode Z5
1342
R(Z5) Ø-Ø
7SA522 Manual
C53000-G1176-C119-2
Setting Options
0.00..30.00 sec
NO
YES
Forward
Reverse
Non-Directional
Inactive
0.05..250.00 Ohm
0.05..250.00 Ohm
0.05..250.00 Ohm
0.00..30.00 sec
0.00..30.00 sec
NO
YES
Forward
Reverse
Non-Directional
Inactive
0.05..250.00 Ohm
0.05..250.00 Ohm
0.05..250.00 Ohm
0.00..30.00 sec
Forward
Reverse
Non-Directional
Inactive
0.05..250.00 Ohm
0.05..250.00 Ohm
0.05..250.00 Ohm
0.00..30.00 sec
Forward
Reverse
Non-Directional
Inactive
0.05..250.00 Ohm
Default Setting
0.00 sec
T1B-multi-ph, delay for multi ph.
faults
YES
Z1B enabled before 1st AR (int.
or ext.)
Forward
Operating mode Z2
2.50 Ohm
R(Z2), Resistance for ph-ph-
faults
5.00 Ohm
X(Z2), Reactance
5.00 Ohm
RE(Z2), Resistance for ph-e
faults
0.30 sec
T2-1phase, delay for single
phase faults
0.30 sec
T2multi-ph, delay for multi phase
faults
NO
Single pole trip for faults in Z2
Reverse
Operating mode Z3
5.00 Ohm
R(Z3), Resistance for ph-ph-
faults
10.00 Ohm
X(Z3), Reactance
10.00 Ohm
RE(Z3), Resistance for ph-e
faults
0.60 sec
T3 delay
Non-Directional
Operating mode Z4
12.00 Ohm
R(Z4), Resistance for ph-ph-
faults
12.00 Ohm
X(Z4), Reactance
12.00 Ohm
RE(Z4), Resistance for ph-e
faults
0.90 sec
T4 delay
Inactive
Operating mode Z5
12.00 Ohm
R(Z5), Resistance for ph-ph-
faults
Functions
Comments
6-55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sa522

Table of Contents