Siemens siprotec 7SA522 User Manual page 387

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

TRIP L1
TRIP L2
TRIP L3
Automatic
Reclosure Inter-
locking
7SA522 Manual
C53000-G1176-C119-2
ping protection function resets very rapidly. Only after the last protection function has
reset (no function is picked up any more) AND the minimum trip command duration
has expired, the trip commands can reset.
A further condition for the reset of the trip command is that the circuit breaker has
opened, in the event of single-pole tripping the relevant circuit-breaker pole. In the
function control of the device this is checked by means of the circuit-breaker position
feedback (Subsection 6.17.2) and the flow of current.
!# UHvÃUSDQÃ8H9
≥1
Figure 6-126 Latching and reset of the trip command
When tripping the circuit-breaker with a protection function the automatic reclosure
must often be blocked until the cause for the protection function operation is found.
7SA522 therefore provides the integrated automatic reclosure interlocking function.
The interlocking state ("/2&.287") will be realized by a RS flipflop which is protected
against auxiliary voltage failure (see Figure 6-127). The RS flipflop will be set via a bi-
nary input "!/RFNRXW 6(7" (FNo 385). With the output alarm "/2&.287" (FNo 530),
if interconnected correspondingly, a reclosure of the circuit-breaker
(e.g. for automatic reclosure, manual close signal, synchronization, closing via control)
can be blocked. Only once the cause for the protection operation is known, should the
interlocking be reset by a manual reset via binary input "!/RFNRXW 5(6(7" (FNo
386).
"'$
FNo
>LOCKOUT Set
"'%
FNo
>LOCKOUT Reset
Figure 6-127 Automatic reclosure interlocking
CB open L1
CB open L2
CB open L3
&
T

FNo
S
Q
LOCKOUT
R
Functions
S
Q
Relay TRIP L1
&
R
S
Q
Relay TRIP L2
&
R
S
Q
Relay TRIP L3
&
R
6-239