Siemens siprotec 7SA522 User Manual page 285

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

Switching on to a
Dead Fault
Fault Detection and
Trip Logic
7SA522 Manual
C53000-G1176-C119-2
Dƒu3ÃTUV7
!%"
I
L1
I
L2
I
L3
L1
L2
L3
!%"!
"D3ÃTUV7
I
E
7131 >I-STUB ENABLE
E
7130 >BLOCK I-STUB
!%"#
7110 >O/C InstTRIP
T
0
switch onto
fault
!%' TPUAÃUv€rÃ9@G6`
Figure 6-80 Logic diagram of the stub protection
To achieve fast tripping following manual closure of the circuit breaker onto a dead
fault, the switch onto fault signal can be routed to the overcurrent protection. The over-
current protection can then trip three-pole without delay or with a reduced delay. It can
be determined via setting parameter for which stage(s) the rapid tripping following
closure on to a dead fault applies. (Refer also to the logic diagrams in Figure 6-77,
6-78 and 6-80, and Sub-section 6.1.3, margin "Circuit Breaker Status").
The fault detection signals of the individual phases (and earth) and the individual stag-
es are combined in such a manner that both the phase information as well as the stage
information of the picked up stages can be output. (Table 6-4).
In the case of the trip signals, the stage which resulted in the trip command is also in-
dicated. If the device has the option to trip single-pole, and this option has been acti-
vated, the pole which has been tripped is also indicated during single-pole tripping (re-
fer also to Sub-section 6.17.4 Overall Tripping Logic of the Device).
!%"
T
&
I
ph
&
!%"" UÃ"D3ÃTUV7
T
&
3I
0
&
DTUV7ÃUryrƒ7D
Yes
≥1
No
Yes
No
!%"$
DTUV7ÃTPUA
UÃDƒuÃTUV7
I-STUB Pickup L1
I-STUB Pickup L2
0
≥1
I-STUB Trip L1
I-STUB Pickup E
0
≥1
I-STUB Trip E
Functions
I-STUB Pickup L3
I-STUB Trip L2
I-STUB Trip L3
6-137