Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

Addr.
Setting Title
140
TripCirc.Superv
201
CT Starpoint
203
Unom PRIMARY
204
Unom SECOND-
ARY
205
CT PRIMARY
206
CT SECONDARY
210
U4 transformer
211
Uph / Udelta
212
Usync connect.
ϕ Usync-Uline
214
215
U-line / Usync
220
I4 transformer
221
I4/Iph CT
230
Rated Frequency
235
PHASE SEQ.
236
Distance Unit
237
Format Z0/Z1
239
T-CB close
240
TMin TRIP CMD
241
TMax CLOSE CMD Power System Data
242
T-CBtest-dead
7SA522 Manual
C53000-G1176-C119-2
Function
Setting Options
Scope of Functions Disabled
1 trip circuit
2 trip circuits
3 trip circuits
Power System Data
towards Line
1
towards Busbar
Power System Data
1.0..1200.0 kV
1
Power System Data
80..125 V
1
Power System Data
10..5000 A
1
Power System Data
1A
1
5A
Power System Data
not connected
1
Udelta transformer
Usync transformer
Ux reference transformer
Power System Data
0.10..9.99
1
Power System Data
L1-E
1
L2-E
L3-E
L1-L2
L2-L3
L3-L1
0..360 °
Power System Data
1
Power System Data
0.80..1.20
1
Power System Data
not connected
1
Neutral Current (of the pro-
tected line)
Neutral Current of the paral-
lel line
Starpoint Curr. of earthed
power transf.
Power System Data
0.010..5.000
1
Power System Data
50 Hz
1
60 Hz
Power System Data
L1 L2 L3
1
L1 L3 L2
Power System Data
km
1
Miles
Power System Data
Zero seq. comp. factors RE/
1
RL and XE/XL
Zero seq. comp. factor K0
and angle(K0)
Power System Data
0.01..0.60 sec
1
Power System Data
0.02..30.00 sec
1
0.01..30.00 sec
1
Power System Data
0.00..30.00 sec
1
Default Setting
Disabled
Trip Circuit Supervision
towards Line
CT Starpoint
400.0 kV
Rated Primary Voltage
100 V
Rated Secondary Voltage (L-L)
1000 A
CT Rated Primary Current
1A
CT Rated Secondary Current
not connected
U4 voltage transformer is
1.73
Matching ratio Phase-VT To Open-
Delta-VT
L1-L2
VT connection for sync. voltage
0 °
Angle adjustment Usync-Uline
1.00
Matching ratio U-line / Usync
Neutral Current (of the pro-
I4 current transformer is
tected line)
1.000
Matching ratio I4/Iph for CT's
50 Hz
Rated Frequency
L1 L2 L3
Phase Sequence
km
Distance measurement unit
Zero seq. comp. factors RE/
Setting format for zero seq.comp. for-
RL and XE/XL
mat
0.06 sec
Closing (operating) time of CB
0.10 sec
Minimum TRIP Command Duration
0.10 sec
Maximum Close Command Duration
0.10 sec
Dead Time for CB test-autoreclosure
Appendix
Comments
B-3