Settings; Information Overview - Siemens siprotec 7SA522 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

Functions

6.13.3 Settings

Adr.
Parameter
3701
FCT Uphase-e
3702
Uph-e>
3704
T Uph-e
3705
T Sen-Imp(Uphe)
3721
FCT 3U0(Ux)
3722
3U0>
3723
3U0 Reset Ratio
3724
T 3U0
3725
T Sen-Imp 3UO

6.13.4 Information Overview

F.No.
Alarm
4308
>BLOCK Uph-e
4309
>BLOCK 3U0
4315
Uph-e OFF
4316
Uph-e BLOCK
4317
Uph-e ACTIVE
4318
3U0 OFF
4319
3U0 BLOCK
4320
3U0 ACTIVE
4341
Uphe PICKUP
4342
Uphe Pickup L1
4343
Uphe Pickup L2
4344
Uphe Pickup L3
4345
Uphe SEND
4350
3U0 PICKUP
4351
3U0 SEND
4361
Uphe TRIP
4362
3U0 TRIP
6-194
Setting options
OFF
Alarm Only
ON
1.0..170.0 V
0.00..30.00 sec
0.05..0.50 sec
OFF
Alarm Only
ON
1.0..300.0 V
0.50..0.95
0.00..30.00 sec
0.05..0.50 sec
>BLOCK Phase-E Overvoltage function
>BLOCK Zero Seq. Overvoltage function
Overvoltage Phase-E is switched OFF
Overvoltage Phase-E is BLOCKED
Overvoltage Phase-E is ACTIVE
Zero Seq.Overvoltage is switched OFF
Zero Seq.Overvoltage is BLOCKED
Zero Seq.Overvoltage is ACTIVE
Overvoltage Phase-E PICKED UP
Overvoltage Phase-E PICKUP L1
Overvoltage Phase-E PICKUP L2
Overvoltage Phase-E PICKUP L3
Overvoltage Ph-E Carrier SendImpulse
Zero Seq. Overvoltage PICKED UP
Zero Seq. OverV. Carrier SendImpulse
Overvoltage Phase-E TRIP command
Overvoltage Zero Seq. TRIP command
Presetting
ON
Phase-Earth Overvoltage
function is
85.0 V
Uph-e> Pickup
2.00 sec
T Uph-e Time Delay
0.25 sec
Time of Carrier Send Impulse
(Uph-e)
OFF
Zero Sequence Overvoltage (or
Ux) is
30.0 V
3U0> (or Ux>) Pickup
0.80
3U0 (or Ux) Reset ratio
2.00 sec
T (3U0 or Ux) Time Delay
0.25 sec
Time of Carrier Send Impulse
(3U0 or Ux)
Comments
Description
7SA522 Manual