Siemens siprotec 7SA522 User Manual page 158

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

Functions
Rated Frequency
Phase Rotation
Units of Length
Mode of Earth Im-
pedance (Residual)
Compensation
6-10
Phase current transformers
Earth current transformer
60 1 ⁄
---------------- -
I
I
=
500 5 ⁄
4
ph CT
• Connection of the I
input to the earth current of the parallel line (for parallel line
4
compensation of the distance protection and/or fault location function, refer to Ap-
pendix A, Figure 1-11):
Address  is then set to: , WUDQVIRUPHU = ,Q SDUDO OLQH and
usually address  is set to ,,SK &7 = 1.
If the set of current transformers on the parallel line however has a different ratio to
those on the protected line, this must be taken into account in address 0221:
Address  is then set so that: , WUDQVIRUPHU = ,Q SDUDO OLQH and
Address  so that ,,SK &7 = I
Example:
Current transformers on protected feeder1200 A
Current transformers on parallel feeder1500 A
1500
------------ -
1.250
I
I
=
=
4
ph
1200
• Connection of the I
4
nection can be used for the polarisation of the directional earth fault protection (refer
to Appendix A, Figure 1-12):
Address  is then set to: , WUDQVIRUPHU = ,< VWDUSRLQW, and
address  ,,SK &7 according to the ratio of the transformation ratios of the
current transformer in the transformer neutral and the set of current transformers on
the protected feeder.
• If the I
input is not required, the following settings are applied:
4
Address  , WUDQVIRUPHU = 1RW FRQQHFWHG,
Address  ,,SK &7 is then irrelevant.
In this case the zero sequence current for the protection functions is computed by
means of the sum of the phase currents.
Address  5DWHG )UHTXHQF\ corresponds to the frequency at which the power
system operates. The preset value is dependent on the model number of the relay pur-
chased, and must be in accordance with the nominal frequency of the power system.
Address  3+$6( 6(4 is used to establish the phase rotation. The preset phase
sequence is "
". For systems that use a phase sequence of "
L1 L2 L3
 must be set accordingly.
Address 0236 Distance Unit corresponds to the units of length (miles or km) applicable
to fault locating. Changing the length unit will not result in an automatic conversion.
The new setting values must be entered at the appropriate addresses.
Matching of the earth to line impedance ratio is an essential prerequisite for the accu-
rate measurement of the fault distance (distance protection, fault location) during earth
faults. In address  )RUPDW == the format for entering the residual compen-
sation is determined. It is possible to either use the ratio 5(5/ and ;(;/ or to enter
the complex earth (residual) impedance factor .. The actual setting of the earth (re-
500 A/5 A
60 A/1 A
0.600
=
N paral. line
input to the neutral current of a power transformer; this con-
/I
.
N prot. line
L1 L3 L2
7SA522 Manual
C53000-G1176-C119-2
", address