Siemens siprotec 7SA522 User Manual page 259

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

Addr.
Setting Title
3163
Dir. BETA
3164
3U0>
3165
IY>
3166
3U2>
3167
3I2>
3170
2nd InrushRest
3171
Imax InrushRest
3172
SOTF Op. Mode
3173
SOTF Time
DELAY
7SA522 Manual
C53000-G1176-C119-2
Setting Options
0..360 °
0.5..10.0 V
0.05..1.00 A
0.5..10.0 V
0.05..1.00 A
10..45 %
0.50..25.00 A
with Pickup (non-directional)
with Pickup and direction
0.00..30.00 sec
The indicated secondary current values for setting ranges and default settings refer to
I
= 1 A. For the nominal current 5 A these values are to be multiplied by 5.
N
Default Setting
122 °
BETA, upper angle for forward
direction
0.5 V
Min. zero seq.voltage 3U0 for
polarizing
0.05 A
Min. earth current IY for polari-
zing
0.5 V
Min. neg. seq. polarizing
voltage 3U2
0.05 A
Min. neg. seq. polarizing cur-
rent 3I2
15 %
2nd harmonic ratio for inrush
restraint
7.50 A
Max.Current, overriding inrush
restraint
with Pickup and
Instantaneous mode after
direction
SwitchOnToFault
0.00 sec
Trip time delay after SOTF
Functions