SIPROTEC
4 Devices
4.13
Time Synchronization
Read-out on the
Operator Control
Panel
4-30
Time tracking in a SIPROTEC
q
DCF77 Radio Receiver (Time Signal from PTB Braunschweig),
q
IRIG-B Radio Receiver (Time Signal from the global positioning satellite (GPS) sys-
tem),
q
signals via the system interface from, for example, a substation control system,
q
radio clock using a system-specific synchronizer box,
q
minute impulses on a binary input.
Time signal generators are connected via a 9-pin D-subminiature port on the back
panel of the device.
Setting of the time synchronization is done exclusively with DIGSI
• Double click on 7LPH 6\QFKURQL]DWLRQ in the data window and enter the set-
tings.
®
Figure 4-26
DIGSI
4, setting of the time synchronization — example
®
Using the SIPROTEC
tings can be retrieved: 0DLQ 0HQX → 6HWWLQJV → 6HWXS([WUDV → &ORFN 6HW
XS.
6(783(;75$6
'DWH7LPH
&ORFN 6HWXS
6HULDO 3RUWV
'HYLFH,'
0/)%9HUVLRQ
&RQWUDVW
Figure 4-27
Read-out of time synchronization settings from the operator control panel
®
4 device can be implemented using:
4 device operator control panel, the time synchronization set-
²!
²!
&/2&. 6(783
²!
2IIVHW
²!
(UURU 7LPH
²!
6RXUFH
²!
®
4:
ka455.gif
.
PLQ
PLQ
,QWHUQDO
7SA522 Manual
C53000-G1176-C119-2