Siemens siprotec 7SA522 User Manual page 581

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

Addr.
Setting Title
2404
I>>>
2501
FCT Weak Infeed
2502
Trip/Echo DELAY
2503
Trip EXTENSION
2505
UNDERVOLTAGE
2601
Operating Mode
2610
Iph>>
2611
T Iph>>
2612
3I0>> PICKUP
2613
T 3I0>>
2614
I>> Telep/BI
2615
I>> SOTF
2620
Iph>
2621
T Iph>
2622
3I0>
2623
T 3I0>
2624
I> Telep/BI
2625
I> SOTF
2630
Iph> STUB
2631
T Iph STUB
2632
3I0> STUB
2633
T 3I0 STUB
2634
I-STUB Telep/BI
2635
I-STUB SOTF
2640
Ip>
2642
T Ip Time Dial
2643
Time Dial TD Ip
2646
T Ip Add
2650
3I0p PICKUP
2652
T 3I0p TimeDial
2653
TimeDial TD3I0p
2656
T 3I0p Add
2660
IEC Curve
7SA522 Manual
C53000-G1176-C119-2
Function
Setting Options
Instantaneous High-
1.00..25.00 A
Speed SOTF Over-
current
Weak Infeed (Trip
OFF
and/or Echo)
Echo only
Echo and Trip
Weak Infeed (Trip
0.00..30.00 sec
and/or Echo)
Weak Infeed (Trip
0.00..30.00 sec
and/or Echo)
Weak Infeed (Trip
2..70 V
and/or Echo)
Backup overcurrent ON
Only Active with Loss of VT
sec. circuit
OFF
Backup overcurrent 0.10..25.00 A
Backup overcurrent 0.00..30.00 sec
Backup overcurrent 0.05..25.00 A
Backup overcurrent 0.00..30.00 sec
Backup overcurrent NO
YES
Backup overcurrent NO
YES
Backup overcurrent 0.10..25.00 A
Backup overcurrent 0.00..30.00 sec
Backup overcurrent 0.05..25.00 A
Backup overcurrent 0.00..30.00 sec
Backup overcurrent NO
YES
Backup overcurrent NO
YES
Backup overcurrent 0.10..25.00 A
Backup overcurrent 0.00..30.00 sec
Backup overcurrent 0.05..25.00 A
Backup overcurrent 0.00..30.00 sec
Backup overcurrent NO
YES
Backup overcurrent NO
YES
Backup overcurrent 0.10..4.00 A
Backup overcurrent 0.05..3.00 sec
Backup overcurrent 0.50..15.00
Backup overcurrent 0.00..30.00 sec
Backup overcurrent 0.05..4.00 A
Backup overcurrent 0.05..3.00 sec
Backup overcurrent 0.50..15.00
Backup overcurrent 0.00..30.00 sec
Backup overcurrent Normal Inverse
Very Inverse
Extremely Inverse
Long time inverse
Default Setting
2.50 A
I>>> Pickup
Echo only
Weak Infeed function is
0.04 sec
Trip / Echo Delay after carrier receipt
0.05 sec
Trip Extension / Echo Impulse time
25 V
Undervoltage (ph-e)
Only Active with Loss of VT
Operating mode
sec. circuit
2.00 A
Iph>> Pickup
0.30 sec
T Iph>> Time delay
0.50 A
3I0>> Pickup
0.30 sec
T 3I0>> Time delay
YES
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after SwitchOnTo-
Fault
1.50 A
Iph> Pickup
0.50 sec
T Iph> Time delay
0.20 A
3I0> Pickup
0.50 sec
T 3I0> Time delay
NO
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after SwitchOnTo-
Fault
0.50 A
Iph> STUB Pickup
0.00 sec
T Iph STUB Time delay
0.20 A
3I0> STUB Pickup
0.00 sec
T 3I0 STUB Time delay
NO
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after SwitchOnTo-
Fault
Ip> Pickup
A
0.50 sec
T Ip Time Dial
5.00
Time Dial TD Ip
0.00 sec
T Ip Additional Time Delay
3I0p Pickup
A
0.50 sec
T 3I0p Time Dial
5.00
Time Dial TD 3I0p
0.00 sec
T 3I0p Additional Time Delay
Normal Inverse
IEC Curve
Appendix
Comments
B-9