Installation and Commissioning
8-16
Table 8-2
Jumper settings for the nominal voltage of the integrated power supply on the
input/output board I/O–1
Jumper
DC 60/110/125 V
X51
X52
X53
Table 8-3
Jumper setting for the quiescent state of the life contact on the
input/output board I/O–1
Jumper
Open in the quiescent state Closed in the quiescent state
X40
For the device in the housing size
relay (R16 and R24) from normally open to normally closed (refer to general dia-
grams in the appendix under Section 1.2) on the input/output
modules I/O–1 without power supply (
Table 8-4
Jumper setting for the quiescent state of the output relay R16 or R24
Jumper
Open in the quiescent state
(normally closed)
X40
1–2
1
Table 8-5
Jumper settings for the Pick-up Voltages of the binary inputs BI1 through BI8,
BI9 through BI16, and BI17 through BI24 on the input/output board I/O–1
Binary Inputs
Jumper
BI1
BI9
BI17
X21/X22
BI2
BI10
BI18
X23/X24
BI3
BI11
BI19
X25/X26
BI4
BI12
BI20
X27/X28
BI5
BI13
BI21
X29/X30
BI6
BI14
BI22
X31/X32
BI7
BI15
BI23
X33/X34
BI8
BI16
BI24
X35/X36
1
) Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2
) Factory settings for devices with power supply voltages of 110 VDC to 250 VDC and 115 VAC
3
) Factory settings for devices with power supply voltages of 220 VDC to 25 VDC and 115 VAC
with power supply
Nominal voltage
DC 110/125/220/250 V
1–2
1–2 and 3–4
1–2
Can be interchanged
with power supply
1–2
1
/
it is possible to change the contact of a particular
1
in slot 19).
Closed in the quiescent state
17 VDC
1
Pick-up
)
L
L
L
L
L
L
L
L
DC 24/48 V
AC 115 V
2–3
Jumpers
2–3
X51 to X53
2–3
are not fitted
Not changeable
2–3
(normally open)
2–3
73 VDC
2
Pick-up
)
M
M
M
M
M
M
M
M
C53000-G1176-C119-2
Presetting
2–3
Presetting
1–2
154 VDC
3
Pick-up
)
H
H
H
H
H
H
H
H