Settings - Siemens siprotec 7SA522 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

Functions
6.1.1.1

Settings

Addr.
Setting Title
201
CT Starpoint
203
Unom PRIMARY
204
Unom SECON-
DARY
205
CT PRIMARY
206
CT SECONDARY
210
U4 transformer
211
Uph / Udelta
212
Usync connect.
ϕ Usync-Uline
214
215
U-line / Usync
220
I4 transformer
221
I4/Iph CT
230
Rated Frequency
235
PHASE SEQ.
236
Distance Unit
237
Format Z0/Z1
239
T-CB close
240
TMin TRIP CMD
241
TMax CLOSE CMD
6-12
Setting Options
towards Line
towards Busbar
1.0..1200.0 kV
80..125 V
10..5000 A
1A
5A
not connected
Udelta transformer
Usync transformer
Ux reference transformer
0.10..9.99
L1-E
L2-E
L3-E
L1-L2
L2-L3
L3-L1
0..360 °
0.80..1.20
not connected
Neutral Current (of the pro-
tected line)
Neutral Current of the paral-
lel line
Starpoint Curr. of earthed
power transf.
0.010..5.000
50 Hz
60 Hz
L1 L2 L3
L1 L3 L2
km
Miles
Zero seq. comp. factors RE/
RL and XE/XL
Zero seq. comp. factor K0
and angle(K0)
0.01..0.60 sec
0.02..30.00 sec
0.01..30.00 sec
Default Setting
towards Line
CT Starpoint
400.0 kV
Rated Primary Voltage
100 V
Rated Secondary Voltage (L-L)
1000 A
CT Rated Primary Current
1A
CT Rated Secondary Current
not connected
U4 voltage transformer is
1.73
Matching ratio Phase-VT To
Open-Delta-VT
L1-L2
VT connection for sync. voltage
0 °
Angle adjustment Usync-Uline
1.00
Matching ratio U-line / Usync
Neutral Current (of
I4 current transformer is
the protected line)
1.000
Matching ratio I4/Iph for CT's
50 Hz
Rated Frequency
L1 L2 L3
Phase Sequence
km
Distance measurement unit
Zero seq. comp.
Setting format for zero
factors RE/RL and
seq.comp. format
XE/XL
0.06 sec
Closing (operating) time of CB
0.10 sec
Minimum TRIP Command Dura-
tion
0.10 sec
Maximum Close Command
Duration
Comments
7SA522 Manual
C53000-G1176-C119-2