Settings - Siemens siprotec 7SA522 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

Functions
6.9.3

Settings

Addr.
Setting Title
2601
Operating Mode
2680
SOTF Time DELAY
2610
Iph>>
2611
T Iph>>
2612
3I0>> PICKUP
2613
T 3I0>>
2614
I>> Telep/BI
2615
I>> SOTF
2620
Iph>
2621
T Iph>
2622
3I0>
2623
T 3I0>
2624
I> Telep/BI
2625
I> SOTF
2640
Ip>
2641
Ip MinT-DELAY
2642
T Ip Time Dial
2643
Time Dial TD Ip
2644
T Ip Time Dial
2645
T Ip Max
2646
T Ip Add
2650
3I0p PICKUP
2651
3I0p MinTdelay
2652
T 3I0p TimeDial
2653
TimeDial TD3I0p
2654
T 3I0p TimeDial
2655
T 3I0Pmax
2656
T 3I0p Add
6-146
Setting Options
ON
Only Active with Loss of VT
sec. circuit
OFF
0.00..30.00 sec
0.10..25.00 A
0.00..30.00 sec
0.05..25.00 A
0.00..30.00 sec
NO
YES
NO
YES
0.10..25.00 A
0.00..30.00 sec
0.05..25.00 A
0.00..30.00 sec
NO
YES
NO
YES
0.10..4.00 A
0.00..30.00 sec
0.05..3.00 sec
0.50..15.00
0.05..15.00 sec
0.00..30.00 sec
0.00..30.00 sec
0.05..4.00 A
0.00..30.00 sec
0.05..3.00 sec
0.50..15.00
0.05..15.00 sec
0.00..30.00 sec
0.00..30.00 sec
Default Setting
Only Active with
Operating mode
Loss of VT sec. cir-
cuit
0.00 sec
Trip time delay after SOTF
2.00 A
Iph>> Pickup
0.30 sec
T Iph>> Time delay
0.50 A
3I0>> Pickup
0.30 sec
T 3I0>> Time delay
YES
Instantaneous trip via Teleprot./
BI
NO
Instantaneous trip after Swit-
chOnToFault
1.50 A
Iph> Pickup
0.50 sec
T Iph> Time delay
0.20 A
3I0> Pickup
0.50 sec
T 3I0> Time delay
NO
Instantaneous trip via Teleprot./
BI
NO
Instantaneous trip after Swit-
chOnToFault
∞ A
Ip> Pickup
1.20 sec
Ip Minimum Time Delay
0.50 sec
T Ip Time Dial
5.00
Time Dial TD Ip
1.35 sec
T Ip Time Dial
5.80 sec
T Ip Maximum Time Delay
0.00 sec
T Ip Additional Time Delay
∞ A
3I0p Pickup
1.20 sec
3I0p Minimum Time Delay
0.50 sec
T 3I0p Time Dial
5.00
Time Dial TD 3I0p
1.35 sec
T 3I0p Time Dial
5.80 sec
T 3I0Pmax Maximum Time
Delay
0.00 sec
T 3I0p Additional Time Delay
Comments
7SA522 Manual
C53000-G1176-C119-2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sa522

Table of Contents