Siemens siprotec 7SA522 User Manual page 583

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

Addr.
Setting Title
3112
T 3I0>>>
3113
3I0>>> Telep/BI
3114
3I0>>>SOTF-Trip
3115
3I0>>>InrushBlk
3120
Op. mode 3I0>>
3121
3I0>>
3122
T 3I0>>
3123
3I0>> Telep/BI
3124
3I0>> SOTF-Trip
3125
3I0>> InrushBlk
3130
Op. mode 3I0>
3131
3I0>
3131
3I0>
3132
T 3I0>
3133
3I0> Telep/BI
3134
3I0> SOTF-Trip
3135
3I0> InrushBlk
3140
Op. mode 3I0p
3141
3I0p PICKUP
3141
3I0p PICKUP
3142
3I0p MinT-DELAY
3143
3I0p Time Dial
3144
3I0p Time Dial
3145
3I0p Time Dial
3146
3I0p MaxT-DELAY
3147
Add.T-DELAY
7SA522 Manual
C53000-G1176-C119-2
Function
Setting Options
Earth fault overcur-
0.00..30.00 sec
rent
Earth fault overcur-
NO
rent
YES
Earth fault overcur-
NO
rent
YES
Earth fault overcur-
NO
rent
YES
Earth fault overcur-
Forward
rent
Reverse
Non-Directional
Inactive
Earth fault overcur-
0.20..25.00 A
rent
Earth fault overcur-
0.00..30.00 sec
rent
Earth fault overcur-
NO
rent
YES
Earth fault overcur-
NO
rent
YES
Earth fault overcur-
NO
rent
YES
Earth fault overcur-
Forward
rent
Reverse
Non-Directional
Inactive
Earth fault overcur-
0.05..25.00 A
rent
Earth fault overcur-
0.003..25.000 A
rent
Earth fault overcur-
0.00..30.00 sec
rent
Earth fault overcur-
NO
rent
YES
Earth fault overcur-
NO
rent
YES
Earth fault overcur-
NO
rent
YES
Earth fault overcur-
Forward
rent
Reverse
Non-Directional
Inactive
Earth fault overcur-
0.05..25.00 A
rent
Earth fault overcur-
0.003..25.000 A
rent
Earth fault overcur-
0.00..30.00 sec
rent
Earth fault overcur-
0.05..3.00 sec
rent
Earth fault overcur-
0.50..15.00
rent
Earth fault overcur-
0.05..15.00 sec
rent
Earth fault overcur-
0.00..30.00 sec
rent
Earth fault overcur-
0.00..30.00 sec
rent
Default Setting
0.30 sec
T 3I0>>> Time delay
NO
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after SwitchOnTo-
Fault
NO
Inrush Blocking
Inactive
Operating mode
2.00 A
3I0>> Pickup
0.60 sec
T 3I0>> Time Delay
NO
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after SwitchOnTo-
Fault
NO
Inrush Blocking
Inactive
Operating mode
1.00 A
3I0> Pickup
1.000 A
3I0> Pickup
0.90 sec
T 3I0> Time Delay
NO
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after SwitchOnTo-
Fault
NO
Inrush Blocking
Inactive
Operating mode
1.00 A
3I0p Pickup
1.000 A
3I0p Pickup
1.20 sec
3I0p Minimum Time Delay
0.50 sec
3I0p Time Dial
5.00
3I0p Time Dial
1.35 sec
3I0p Time Dial
5.80 sec
3I0p Maximum Time Delay
1.20 sec
Additional Time Delay
Appendix
Comments
B-11