Siemens siprotec 7SA522 User Manual page 82

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

®
SIPROTEC
4 Devices
Setting Sequence
4-18
/2$' 3$5$0(7(5


'RZQORDG DFWLYH
Screen of Device during Settings Transfer
Figure 4-13
When setting a SIPROTEC
q
Specify the interfaces, the device data, and the time synchronization,
q
Determine the device functions to be used,
q
Design the assignment of the inputs and outputs using the configuration matrix,
q
Design all of the special logic that is to be employed using CFC (optional),
q
Enter the power system data,
q
Apply the settings to groups A to D (groups B to D optional),
q
Set the passwords.
Setting steps partially build on the decisions from the previous steps. By following the
sequence listed, unnecessary changes and rework are avoided. The sequence en-
sures that information required for an individual step will be available.
To design the control display, for example, the physical connections between the de-
vice and the primary equipment must be known. These connections are determined
and setup during configuration of the inputs and outputs in the matrix. During the dis-
play design, simply select the relevant available equipment indications, and assign
these indications with selected graphic symbols.
Note:
Changes to the configuration matrix and the control display are protected by password
No. 7 (Password for parameter set).
®
4 device, adhere to the following sequence: