Siemens siprotec 7SA522 User Manual page 271

Distance protection
Hide thumbs Also See for siprotec 7SA522:
Table of Contents

Advertisement

Time Settings
Transient Blocking
7SA522 Manual
C53000-G1176-C119-2
A is distributed equally on the line ends B and C. The setting value ,R0LQ 7HOH
SURW (address ), which is decisive for the echo or the blocking signal, must
therefore be set smaller than one half of the setting value for the earth current stage
used for teleprotection. In addition, the above comments regarding the capacitive
earth current which is left out in Figure 6-74 apply. If the earth current distribution is
different from the distribution assumed here, the conditions are more favourable as
one of the two earth currents I
scribed previously.
A
I
= I
EA
Figure 6-74 Possible unfavourable current distribution on a three terminal line during an exter-
nal earth fault.
The send signal prolongation 6HQG 3URORQJ (address ) must ensure that the
transmitted signal reliably reaches the opposite line end, even if tripping is very fast at
the sending line end and/or the signal transmission time (channel delay) is relatively
long. In the case of the permissive schemes 'LU&RPS3LFNXS and 81%/2&.,1*
this signal prolongation only comes into effect if the device has already issued a trip
command. This ensures the release of the other line end even if the short-circuit is
cleared very rapidly by a different protection function or other stage. In the case of the
blocking scheme %/2&.,1* the transmit signal is always prolonged by this time. In
this case it corresponds to a transient blocking following a reverse fault. This setting
can only be modified with DIGSI
The release of the directional tripping can be delayed by means of the permissive sig-
nal delay 7 9 (address ). This is only required for the blocking scheme %/2&.
,1* to allow sufficient transmission time for the blocking signal during external faults.
This delay only has an effect on the receive circuit of the teleprotection; conversely
tripping by the comparison protection is not delayed by the set time delay of the direc-
tional stage.
The setting parameters 7U%ON :DLW 7LPH and 7U%ON %ORFN7LPH are for the tran-
sient blocking with the comparison protection. This setting can only be modified with
®
DIGSI
4 under "Additional Settings".
The time 7U%ON :DLW 7LPH (address ) is a waiting time prior to transient block-
ing. In the case of the permissive schemes, only once the directional stage of the earth
fault protection has recognized a fault in the reverse direction, within this period of time
after fault detection, will the transient blocking be activated. In the case of the blocking
scheme, the waiting time prevents transient blocking in the event that the blocking sig-
nal reception from the opposite line end is very fast. With the setting ∞ there is no tran-
sient blocking.
or I
must then be larger than in the situation de-
EB
EC
+ I
EB
EC
I
EC
®
4 under "Additional Settings".
Functions
B
I
EB
6-123

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7sa522

Table of Contents