Mechanical Installation; Installation Environment - YASKAWA V1000 Quick Start Manual

Ac drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

2.1 Mechanical Installation

2.1
Mechanical Installation
This section outlines specifications, procedures, and environment for proper mechanical
installation of the drive.
u

Installation Environment

To help prolong the optimum performance life of the drive, install the drive in the proper
environment.
Table 2.1
Environment
Installation Area
Ambient
Temperature
Humidity
Storage Temperature -20 °C to +60 °C
Surrounding Area
Altitude
Vibration
Orientation
NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during
installation and project construction. Failure to comply could result in damage to the drive. Place a temporary
cover over the top of the drive during installation. Remove the temporary cover before startup, as the cover
will reduce ventilation and cause the drive to overheat.
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive. Failure to
comply could result in erroneous operation. If such devices must be used in close proximity to the drive, take
proper steps to shield the drive from noise.
40
describes the appropriate environment for the drive.
Table 2.1 Installation Environment
Indoors
IP20/NEMA Type 1 enclosure: -10 °C to +40 °C
IP20/IP00 Open-Chassis enclosure: -10 °C to +50 °C
Finless Type: IP20/IP00 enclosure: -10 °C to +50 °C
NEMA Type 4X/IP66 enclosure: -10 °C to +40 °C
Drive reliability improves in environments without wide temperature fluctuations.
When using an enclosure panel, install a cooling fan or air conditioner in the area to ensure
that the air temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
Up to 1000 meters without derating; up to 3000 meters with output current, ambient
temperature, and voltage derating.
2
10 to 20 Hz at 9.8 m/s
2
20 to 55 Hz at 5.9 m/s
Install the drive vertically to maintain maximum cooling effects.
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
Conditions