YASKAWA V1000 Quick Start Manual page 213

Ac drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

Model
CIMR-
Terminal
Vo2A
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
0001
0002
–, +1, +2
0004
0006
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
0010
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
0012
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
0020
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
0030
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
0040
B1, B2
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
Table C.3 Wire Gauge and Torque Specifications
Recomm.
Gauge
AWG, kcmil
14
14
14
12
14
10
12
14
10
10
10
10
8
8
8
6
8
6
C.2 UL and CSA Standards
Screw
Wire Range
Size
AWG, kcmil
18 to 14
18 to 14
18 to 14
M3.5
18 to 14
18 to 14
14 to 10
14 to 10
14 to 10
M4
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
M4
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
M4
14 to 10
14 to 10
10 to 6
10 to 6
M4
10 to 6
14 to 10
10 to 6
M5
10 to 6
10 to 6
M4
10 to 6
14 to 10
10 to 6
M5
Tightening
Torque
N•m (lb.in.)
0.8 to 1.0
(7.1 to 8.9)
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
2.1 to 2.3
(18.6 to 20.4)
2 to 2.5
(17.7 to 22.1)
2.1 to 2.3
(18.6 to 20.4)
2 to 2.5
(17.7 to 22.1)
C
213

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents