B.1 Parameter Table
No.
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
H1-oo
Function
Setting
0
3-Wire Sequence
1
Local/Remote Selection
2
External Reference 1/2
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
7
Accel/Decel Time 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Drive Overheat Alarm (oH2)
C
Terminal A1/A2 Enable
F
Not used
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
182
Name
H1 Multi-Function Digital Input Selections
Closed: Reverse rotation (only for 3-wire sequence)
Open: Remote, Reference 1 or 2 (b1-01/02 or b1-15/16)
Closed: Local, LED operator is run and reference source
Open: Run and frequency reference source 1 (b1-01/02)
Closed: Run and frequency reference source 2 (b1-01/02)
Used to select Multi-Step Speeds set in d1-01 to d1-16
Open: Selected speed reference
Closed: Jog Frequency reference (d1-17). Jog has priority over all other
reference sources.
Used to switch between Accel/Decel. Time 1/2
Open: Normal operation
Closed: No drive output
Open: No drive output
Closed: Normal operation
Closed: The drive pauses during acceleration or deceleration and maintains
the output frequency.
Closed: Displays an oH2 alarm
Terminal status differs depending on drive software version.
PRG: 1016 and later:
Open: Analog input selected by H3-14 is disabled.
Closed: Analog input selected by H3-14 is enabled.
PRG: 1015 and earlier:
Open: Analog inputs selected for terminals A1 and A2 are disabled.
Closed: Analog inputs selected for terminals A1 and A2 are enabled.
Select this setting when not using the terminal or when using the terminal
in a pass-through mode.
Open: Maintains the current frequency reference
Closed: Increases or decreases the current frequency reference
Closed: Runs forward at the Jog Frequency d1-17.
Closed: Runs reverse at the Jog Frequency d1-17.
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
Description
Selects function of terminal S3
Selects function of terminal S4
Selects function of terminal S5
Selects function of terminal S6
Selects function of terminal S7
Description