Use H2 parameters to assign functions to the multi-function digital outputs.
H2-01
Terminal MA, MB and MC Function Selection (relay)
H2-02
Terminal P1 Function Selection (open-collector)
H2-03
Terminal P2 Function Selection (open-collector)
H2-06
Watt Hour Output Unit Selection
H2-oo
Function
Setting
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
8
During Baseblock (N.O.)
9
Frequency Reference Source
A
Run Command Source
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
D
Braking Resistor Fault
E
Fault
F
Not used/Through Mode
10
Alarm
11
Reset Command Active
12
Timer Output
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
Name
H2: Multi-Function Digital Outputs
H2 Multi-Function Digital Output Settings
Closed: A Run command is active or voltage is output.
Closed: Output frequency is 0.
Closed: Output frequency equals the speed reference (plus or minus the
hysteresis set to L4-02).
Closed: Output frequency and speed reference equal the value in L4-01
(plus or minus the hysteresis of L4-02).
Closed: Output frequency is less than or equal to the value in L4-01 with
hysteresis determined by L4-02.
Closed: Output frequency is greater than or equal to the value in L4-01,
with hysteresis determined by L4-02.
Closed: Drive Ready. The drive is powered up, not in a fault state, and
in the Drive mode.
Closed: DC bus voltage is below the UV trip level set in L2-05.
Closed: This is no output voltage
Closed: Digital operator supplies the frequency reference.
Open: Reference 1 or 2 are active
Closed: Digital operator supplies the run command.
Closed: Output current/torque exceeds the torque value set in parameter
L6-02 for longer than the time set in parameter L6-03.
Closed: Loss of the analog frequency reference detected. Enabled when
L4-05 = 1.
Closed: Braking resistor or transistor is overheated or faulted out.
Closed: Fault occurred (other than CPF00 and CPF01).
Set this value when the terminal is not used, or when using the terminal
in the pass-through mode.
Closed: An alarm is triggered.
Closed: Reset command to the drive is active.
Timer output, controlled by b4-01 and b4-02. Used in conjunction with
the digital input (H1-
B.1 Parameter Table
Description
Refer to "Multi-Function Digital
Output Selection Table" for a
description of setting values.
Refer to V1000 Tech Manual.
Description
= 18 "timer function").
Range
0 to 192
0 to 4