The contactor on the inrush
prevention circuit is damaged.
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur.
• Check monitor U4-06 for the performance life of the inrush prevention circuit.
• Replace the drive if U4-06 exceeds 90%.