H2-oo
Function
Setting
4C
During Fast-stop
4D
oH Pre-alarm Time Limit
4E
Braking Transistor Fault (rr)
4F
Braking Resistor Overheat (oH)
90 to 92 DriveWorksEZ Digital Output 1
to 3
H2 Parameter Functions
100 to
Reversed Output Switching of 0
192
to 92
No.
Use H3 parameters to set the multi-function analog input terminals.
H3-01
Terminal A1 Signal Level Selection
H3-02
Terminal A1 Function Selection
H3-03
Terminal A1 Gain Setting
H3-04
Terminal A1 Bias Setting
H3-09
Terminal A2 Signal Level Selection
H3-10
Terminal A2 Function Selection
H3-11
Terminal A2 Gain Setting
H3-12
Terminal A2 Bias Setting
H3-13
Analog Input Filter Time Constant
Analog Input Terminal Enable
H3-14
Selection
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
H2 Multi-Function Digital Output Settings
Closed: Fast-stop command is entered
Closed: oH Pre-alarm time limit is passed.
Closed: The built-in dynamic braking transistor failed.
Note: Available in drive software versions PRG: 1016 and later.
Closed: The dynamic braking resistor overheated.
Note: Available in drive software versions PRG: 1016 and later.
These settings are for digital output functions used in DriveWorksEZ.
Normally there is no need to change or apply these settings.
Reverse the output switching of the multi-function output functions. Set
the last two digits of 1oo to reverse the output signal of that specific
function.
Name
H3: Analog Inputs
0: 0 to +10 V (lower limit)
1: 0 to +10 V (no lower limit)
Sets the function of terminal A1.
Sets the level of the input value selected in H3-02 when 10V is input
at terminal A1.
Sets the level of the input value selected in H3-02 when 0V is input
at terminal A1.
Sets the input signal level for terminal A2.
0: 0 to +10 V (with lower limit)
1: 0 to +10 V (no lower limit)
2: 4 to 20 mA
3: 0 to 20 mA
Sets the function of terminal A2.
Sets the level of the input value selected in H3-10 when 10 V (20
mA) is input at terminal A2.
Sets the level of the input value selected in H3-10 when 0 V (0 or 4
mA) is input at terminal A2.
Sets the primary delay filter time constant for terminals A1 and A2.
Used for noise filtering.
Determines which analog input terminal or terminals will be enabled
when a digital input programmed for "Analog input enable" (H1o-
oo = C) is activated.
1: Terminal A1 only
2: Terminal A2 only
7: All terminals enabled
Note: Available in drive software versions PRG: 1016 and later.
B.1 Parameter Table
Description
Description
B
187