YASKAWA V1000 Quick Start Manual page 77

Ac drive
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

Setting Value
V (left position)
I (right position)
No.
Parameter Name
H3-09 Frequency ref. (current)
terminal A2 signal level selection
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
Figure 3.22 DIP Switch S1
Table 3.13 DIP Switch S1 Settings
Voltage input (0 to 10 V)
Current input (4 to 20 mA or 0 to 20 mA): default setting
Table 3.14 Parameter H3-09 Details
Selects the signal level for terminal A2.
0: 0 to +10 V, unipolar input (with lower limit)
1: 0 to +10 V, bipolar input (no lower limit)
2: 4 to 20 mA
3: 0 to 20 mA
3.7 Main Frequency Reference
V
I
Description
Description
Setting
Default
Range
Setting
0 to 3
2
3
77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents