C.2 UL and CSA Standards
Terminal
Wire Gauge
Screws
18 AWG
M3.5
16 AWG
M3.5
M3.5
14 AWG
M4
M4
12 / 10 AWG
M5
M4
8 AWG
M5
M8
M4
M5
6 AWG
M6
M8
M6
4 AWG
M8
3 AWG
M8
2 AWG
M8
<1>
Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using
two sets for each connection.
Example: Models with 14 AWG for both input and output require one set for input terminals and one set for
output terminals, so the user should order two sets of [100-066-218].
Note:
Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the
voltage drop is greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal
block. Use the following formula to calculate the amount of voltage drop:
Line drop voltage (V) = 3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10
n
Factory Recommended Branch Circuit Protection
Yaskawa recommends installing one of the following types of branch circuit protection to
maintain compliance with UL508C. Semiconductor protective type fuses are preferred.
Alternate branch circuit protection devices are also listed in
Branch circuit protection shall be provided by any of the following:
• Non-time delay Class J, T, or CC fuses sized at 300% of the drive input rating
Note: The following model/fuse combinations are excluded from the preceding statement:
2A0002/A6T6, 2A0004/A6T15, 4A0004/A6T15, 4A0005/A6T20, and 4A0007/A6T25.
• Time delay Class J, T, or CC fuses sized at 175% of the drive input rating
• Time-delay Class RK5 fuses sized at 225% of the drive input rating
216
Table C.5 Closed-Loop Crimp Terminal Sizes
Crimp
Terminal
Model
Machine No.
Number
R1.25-3.5
YA-4
R1.25-3.5
YA-4
R2-3.5
YA-4
R2-4
YA-4
R5.5-4
YA-4
R5.5-5
YA-4
8-4
YA-4
R8-5
YA-4
R8-8
YA-4
14-4
YA-4
R14-5
YA-4
R14-6
YA-5
R14-8
YA-5
R22-6
YA-5
R22-8
YA-5
R38-8
YA-5
R38-8
YA-5
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
Tool
Insulation
Die Jaw
Model No.
AD-900
AD-900
AD-900
AD-900
AD-900
AD-900
AD-901
AD-901
AD-901
AD-902
AD-902
AD-952
AD-952
AD-953
AD-953
AD-954
AD-954
Table
C.6.
<1>
Cap
Code
TP-003
100-066-217
TP-003
100-066-217
TP-003
100-066-218
TP-003
100-054-028
TP-005
100-054-029
TP-005
100-054-030
TP-008
100-054-031
TP-008
100-054-032
TP-008
100-061-111
TP-014
100-66-220
TP-014
100-054-034
TP-014
100-051-261
TP-014
100-054-035
TP-022
100-051-262
TP-022
100-051-263
TP-038
100-051-264
TP-038
100-051-264
-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents