4.6 Basic Drive Setup Adjustments

4.6

Basic Drive Setup Adjustments

This section explains the basic settings required for initial drive operation. Checking these
basic parameter settings during start-up will help to ensure a successful drive start-up.
If more information is required for parameters not listed in this section,
List on page 167
as required for a complete listing of drive parameters.
u

Control Mode Selection: A1-02

Note:
1. Be sure to perform Auto-Tuning when using one of the vector control modes.
2. Reinitializing the drive does not reset A1-02 to the factory default value.
n
Available Control Modes
Three motor control modes are available. Select the control mode that best suits the application
in which the drive will be used.
Control Mode
V/f Control
Open Loop Vector Control
PM Open Loop Vector Control
u

Initialize Parameter Values: A1-03

Parameter A1-03 (Initialize Parameters) resets all parameters to the original default values.
Note:
1. Save all changed parameter settings by setting o2-03 = "1" before initializing the drive. Settings will
be lost if performing a 2-Wire or 3-Wire initialization using 2220 or 3330 if user parameters are not
saved first.
2. If using Open Loop Vector Control (A1-02 = 2), Auto-Tuning will need to be performed again after
the drive is initialized.
n
Different Methods of Drive initialization
1110: Resets all parameters to user-defined default values
A user-initialization resets all parameters to a user-defined set of default values previously
saved to the drive. Set parameter o2-03 to "2" to clear those values.
Note:
Set o2-03 to "1" to save the current parameter settings and changes for a "user-initialization." After
saving all parameter setting changes, parameter o2-03 automatically returns to 0. .
106
Parameter
• General variable speed applications
A1-02 = 0
• For running multiple motors from a single drive
(default)
• When replacing a drive in which parameter settings are
unknown.
• General variable speed applications
A1-02 = 2
• Applications requiring high precision, high speed control.
Variable torque applications employing permanent magnet motors
A1-02 = 5
and energy savings.
Refer to Auto-Tuning on page 113
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
Refer to Parameter
Main Applications
for details.