B.1 Parameter Table
No.
H3-16
Terminal A1 Offset
H3-17
Terminal A2 Offset
H3-oo
Setting
0
Frequency Bias
1
Frequency Gain
2
Auxiliary Frequency Reference (used as multi-step speed 2)
4
Output Voltage Bias
7
Overtorque/Undertorque Detection Level
B
PID Feedback
C
PID Set Point
E
Motor Temperature (PTC input)
F
Not used/Through Mode
10
FWD Torque Limit
11
REV Torque Limit
12
Regenerative Torque Limit
15
FWD/REV Torque Limit
16
Differential PID Feedback
30/31
DriveWorksEZ Analog Input 1/2
Output Voltage Gain
41
Note: Function available in versions PRG: 1016 and later.
No.
Use H4 parameters to configure the multi-function analog output terminals.
Multi-Function Analog Output
H4-01
Terminal AM)
Multi-Function Analog Output
H4-02
Terminal AM Gain
188
Name
H3 Multi-Function Analog Input Settings
Function
Name
H4: Multi-Function Analog Outputs
Selects data output via multi-function analog output terminal AM.
Sets terminal AM output level when selected monitor is at 100%.
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
Enter a 0 V signal to terminal A1. Next adjust the offset in H3-16
until the monitor U1-13 for the terminal A1 input voltage reads 0.0%.
The process is the same for terminal A2.
Note: Available in drive software versions PRG: 1016 and later.
Enter a 0 V signal, and adjust the offset for terminal A2 in H3-17
until the monitor U1-14 for terminal A2 input voltage reads 0.0%.
Note: Available in drive software versions PRG: 1016 and later.
Description
Maximum Input Level Possible
Max output frequency (E1-04).
Frequency reference (voltage)
Max output frequency (E1-04)
200 V Class: 200 V
400 V Class: 400 V
Open Loop Vector: Motor rated torque
V/f control: Drive rated current
10V = 100%
10V = 100%
10 V = 100.00%
Motor rated torque
Motor rated torque
Motor rated torque
Motor rated torque
10 V = 100%
These settings are for analog output
functions used in DriveWorksEZ.
Normally there is no need to change or
apply these settings.
10 V = 100.00%