Item
CIMR-Vo4A
Maximum Applicable Motor
<1>
Capacity (HP)
Input
Input Current (A)
Output Current (kVA)
<3>
Output Current (A)
Output
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
Rated Voltage Rated Frequency
Power
Allowable Voltage Fluctuation
Supply
Allowable Frequency Fluctuation
Harmonic Corrective Actions DC Link Choke
<1>
The motor capacity (HP) refers to a NEC 4-pole motor. The rated output current of the drive output amps should
be equal to or greater than the motor rated current.
<2>
Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and
power supply impedance.
<3>
Rated motor capacity is calculated with a rated output voltage of 440 V.
<4>
Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required in order to raise the carrier
frequency.
<5>
Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
Table A.5 Power Ratings Continued
0011
ND Rating
7.5
HD Rating
5.0
ND Rating
14.0
<2>
HD Rating
10.4
ND Rating
8.5
<4>
HD Rating
7.0
<5>
ND Rating
11.1
<4>
HD Rating
9.2
<5>
(Derating may be required for applications that start and stop
Three-phase: 380 to 480 V (proportional to input voltage)
A.3 Three-Phase 400 V Class Drives
Specification
0018
0023
10.0
15.0
10.0
10.0
20.0
24.0
15.0
20.0
13.3
17.5
11.3
13.7
17.5
23.0
14.8
18.0
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
frequently)
User-adjustable 2 to 15 kHz
400 Hz (user-adjustable)
Three-phase: 380 to 480 V 50/60 Hz
-15 to 10%
±5%
Optional
0031
0038
20.0
25.0
15.0
20.0
38.0
44.0
29.0
39.0
23.6
29.0
18.3
23.6
31.0
38.0
24.0
31.0
161