Parts and Tools Required for Connecting an EX Series Switch to Earth Ground
Table 56: Parts and Tools Required for Connecting an EX Series Switch to Earth Ground
Earthing
Terminal
Grounding Cable
Switch
Location
Requirements
EX2200
Rear panel
14 AWG (2 mm²),
of chassis
minimum 90°C wire,
or as permitted by
the local code
EX3200
Rear panel
14 AWG (2 mm²),
of chassis
minimum 90°C wire,
or as permitted by
the local code
EX3300
Rear panel
14 AWG (2 mm²),
of chassis
minimum 90°C wire,
or as permitted by
the local code
EX4200
Left side of
14 WG (2 mm²),
chassis
minimum 90°C wire,
or as permitted by
the local code
140
Table 56 on page 140
lists the earthing terminal location, grounding cable requirements,
grounding lug specifications, screws and washers required, and the screwdriver needed
for connecting a switch to earth ground. Before you begin connecting a switch to earth
ground, ensure you have the parts and tools required for your switch.
Grounding Lug
Specifications
Panduit
LCC10-14BWL or
equivalent—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
Screws and
Washers
Screwdriver
Two 10-32
Phillips (+)
x .25 in. screws
number 2
with #10
split-lock
washer—
not provided
Two #10 flat
washers—not
provided
Two 10-32
Phillips (+)
x .25 in. screws
number 2
with #10
split-lock
washer—
not provided
Two #10 flat
washers—
not provided
Two 10-32
Phillips (+)
x .25 in. screws
number 2
with #10
split-lock
washer—
not provided
Two #10 flat
washers—
not provided
Two 10-32
Phillips (+)
x .25 in. screws
number 2
with #10
split-lock
washer—
not provided
Two #10 flat
washers—
not provided
Copyright © 2015, Juniper Networks, Inc.
Additional
Information
See
"Special
Instructions to
Follow Before
Connecting Earth
Ground to a Switch"
on page
142.
See
"Special
Instructions to
Follow Before
Connecting Earth
Ground to a Switch"
on page
142.