Mitsubishi 00JCPU User Manual page 391

Q series programmable controller
Table of Contents

Advertisement

(b) Processing after annunciator on
1) Data stored in the special register (SD62 to SD79)
• Turned-on annunciator numbers are stored in SD64 to SD79 in order.
• The annunciator number in SD64 is stored in SD62.
• SD63 value is incremented by "1".
SD62
SD63
SD64
SD65
SD66
SD67
SD79
2) Processing on the CPU
• When using the Basic model QCPU:
The ERR LED on the front side turns on.
• When using the High Performance model QCPU, Process CPU, or Redundant CPU:
The USER LED on the front side turns on (red).
3) On/off setting for the LED
By setting indication priority for an error in SD207 to SD209, whether to turn on the USER. LED (the ERR.
LED for the Basic model QCPU) or not when the annunciator is turned on can be set.
(
Section 6.21.2)
SET F50
SET F25 SET F1023
0
50
50
0
1
2
0
50
50
0
0
25
0
0
0
1023
0
0
0
0
0
0
Figure 9.12 Processing after annunciator ON
50
3
50
25
Up to 16 annunciator
0
numbers can be stored.
0
CHAPTER9 DEVICES
9
9 - 16

Hide quick links:

Advertisement

Table of Contents
loading