Mitsubishi 00JCPU User Manual page 476

Q series programmable controller
Table of Contents

Advertisement

(1) Devices that can be used as local devices
The following devices can be used as local devices.
• Internal relay (M)
• Edge relay (V)
• Timer (T, ST)
• Counter (C)
• Data register (D)
(2) Saving and restoring a local device file
When some programs use a local device, respective local device file data in the standard RAM or a memory card
(SRAM) are exchanged with the device memory data of the CPU module after execution of each program.
For this reason, the scan time increases by the time spent for data exchange.
Sequence program
Local device
For
program A
For
program B
For
program C
Remark
1.
There are some instructions for which a local device cannot be specified.
For details, refer to the pages describing devices available for each instruction in the following manual.
2.
For the concept of the number of words used for the local devices, refer to Section 9.2.
9 - 101
Program A
Restored
Local device
For
program A
For
program B
For
program C
Figure 9.99 Saving and restoring local device files
MELSEC-Q/L Programming Manual (Common Instruction)
Program B
Saved
Restored
Saved
Local device
For
program A
For
program B
For
program C
Program C
Restored

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents