Mitsubishi 00JCPU User Manual page 517

Q series programmable controller
Table of Contents

Advertisement

Set the RUN/STOP switch to STOP,
turn the RESET/L.CLR switch to reset
clear position, and power on the CPU module.
(the ERR. LED turns on).
Select [Online]
in GX Developer and format
the program memory.
To write the parameters, created program, and
initial device value, make settings in the Write to
PLC screen displayed by selecting
[Online]
[Write to PLC] in GX Developer.
Power off the programmable controller
and then on or reset the CPU module.
Set the RUN/STOP switch to RUN to
change the CPU module in the RUN status.
NO
Is the ERR. LED on
the CPU module on
Check the error cause in the System Monitor
screen displayed by selecting [Diagnostics]
[System Monitor] in GX Developer or in the
"PLC diagnostics" screen and remove the error.
NO
Start boot operation?
To Section 11.2.5
End
Figure 11.5 Flowchart for writing one program
*1: The parameter-valid drive is set to the program memory (drive 0) with the DIP switches by default (SW2: Off, SW3: On).
To store parameters in the standard ROM or memory card, change the settings of the DIP switches.
*2: For procedures when the Redundant CPU is used, refer to the following.
QnPRHCPU User's Manual (Redundant System)
*3: When storing the file register and initial device value to the standard RAM or memory card (except the Flash card), format
the memory used.
*4: Write each data in the memory as shown below:
• Program: Program memory
• Parameter: Memory set in the parameter-valid drive
• Initial device value: Memory set in the PLC file tab of the PLC parameter dialog box
CHAPTER11 PROCEDURES FOR WRITING PROGRAM TO CPU MODULE
1)
[Format PLC memory]
*3
*4
(flashing)?
YES
YES
Write to PLC screen
QCPU User's Manual
(Hardware Design, Maintenance and Inspection)
QCPU User's Manual
(Hardware Design, Maintenance and Inspection)
1
2
11
4
5
6
7
8
11 - 11