Mitsubishi 00JCPU User Manual page 230

Q series programmable controller
Table of Contents

Advertisement

In multiple CPU systems, inputs and outputs of control modules can forcibly turned on/off.
Even when inputs and outputs of non-control modules are registered for forced on/off, the input/output devices in other CPU
modules and inputs and outputs of modules controlled by other CPU modules cannot be forcibly turned on/off. (The input/
output devices in the host CPU module can forcibly turned on/off.)
(d) Cancelling on/off registration data
The registered forced ON/OFF data can be canceled by GX Developer.
Once the registered data is canceled, the status of the forced on/off registered devices will be as follows.
Forced on/off registered device
Input from modules mounted on the base unit
Input of the CPU module to be refreshed from LX
of a CC-Link IE Controller Network or
MELSECNET/H module
Input
Input of the CPU module to be refreshed from
RX of a CC-Link module
Input other than above (outside of the refresh
range)
Output from modules mounted on the base unit
Output of the CPU module to be refreshed from
LY of a CC-Link IE Controller Network or
MELSECNET/H module
Output
Output of the CPU module to be refreshed from
RY of a CC-Link module
Output other than above (outside of the refresh
range)
Forced on/off setting can be cleared by:
• powering off and then on the CPU module,
• resetting the CPU module by the RUN/STOP/RESET switch, or
• resetting the CPU module by the remote RESET operation.
6 - 50
Table6.14 Status of devices after forced on/off registration data is canceled
Sequence program operations
(on/off) performed
Uses the on/off status input from modules.
Used the on/off status refreshed via CC-Link IE Controller Network or
MELSECNET/H.
Uses the on/off status refreshed via CC-Link.
Uses the results of sequence
program operations.
Outputs the results of sequence
program operations.
Outputs the results of sequence
program operations. (The results
are not output externally.)
Sequence program operations
(on/off) not performed
Holds the forced on/off status.
Holds the registered on/off status.
Holds the forced on/off status.

Hide quick links:

Advertisement

Table of Contents
loading